Gas Detection
The role of combustible and toxic gas detectors in industrial plant safety
Jun 24 2019
Author: Jon D. Miller on behalf of Det-Tronics
Free to read
Articles are free to download. Unlock the article to be shown more content, graphs and images.
Hydrogen, a combustible gas, is colorless, odorless, tasteless and non-toxic, but hydrogen is ranked highest on the National Fire Protection Agency (NFPA’s) flammability scale because it is flammable if even small amounts are mixed with air. Low concentrations of toxic gases such as ammonia can trigger coughing and nose and throat irritation, while high concentrations cause immediate burning of the eyes, nose, throat and respiratory tract, and can result in blindness, lung damage or death. Chlorine, though not flammable alone, can react explosively or form explosive compounds with other chemicals such as turpentine and ammonia.
These and myriad other combustible and toxic gases are found in industrial processing and manufacturing settings — whether they are used in the actual processing or are byproducts of processes. That’s why industrial plants need a gas detection network to mitigate risk in all areas where combustible or toxic gases could create a workplace hazard for life safety.
Gas Detection and Notification
Techniques for Risk Mitigation
Life safety gas detection systems require not only the ability to detect leaking combustible or toxic gases — but also to mitigate risk through action.
According to IEC 60079-29 Series standards and IEC 62990 Series standards under development, a life safety gas system does more than detect the presence of combustible and toxic gases. It must be able to provide alarm notification if data from the gas detectors hits a certain threshold. It must also have the ability to take corrective actions such as increasing ventilation, closing a valve or door, or de-energizing equipment to mitigate risk.
In life safety systems, gas detectors tend to have feature-rich displays as well as smart capabilities that improve digital information transfers. The gas detectors are connected to a safety system controller (SSC) and various other devices that can take a number of different actions in order to help bring a dangerous situation back to a safe state.
The SSC for risk mitigation systems receives and interprets input from multiple gas detectors and decides whether or not some action needs to be taken. In order to prevent nuisance alarms, the SSC may discount information from a single detector if it is not confirmed by data from other detectors in the same area. The SSC must be IEC 60079-29 Series and/or IEC 62990 Series compliant as applicable to ensure that signaling, control, notification, and activations can be depended upon for life safety during adverse conditions.
Portable and transportable gas detectors will further mitigate personnel risk by ensuring full detection coverage in all areas of the workplace.
Risks of Combustible and Toxic Gases
Combustible gases are those that can cause a fire or explosion if the gas is exposed to an ignition source such as a spark, a hot surface, an open flame or even friction caused by gas escaping through a pipe fissure. Combustible gases include hydrocarbons and hydrogen.
A toxic gas can cause harm to humans, ranging from minor irritation to death. Toxic gases include, but are not limited to, hydrogen sulfide, carbon monoxide, nitrogen dioxide, ammonia and chlorine. Even at low concentrations measured in parts per million, certain toxic gases can cause death by poisoning caused by exposure to carbon dioxide or by asphyxiation. Many gases are both combustible and toxic.
From a risk mitigation perspective, there is a hierarchy of risk that should be considered when designing a plant’s hazardous-area gas detection system. The “Risk Mitigation” chart above ranks the risk mitigation objectives in priority order, and describes the type(s) of gas detection required for each objective.
Product & Performance Standards and Certifications
Because life safety gas detection equipment is used in high-risk areas, each component has to be product certified for hazardous locations as well as performance certified for the specific attributes and functions required.
Before embarking on the design of a life safety gas detection system, plant engineers should also review applicable safety standards, which can provide the backbone of a plan to help ensure continuous safe operation of plant processes. Standards address which devices and systems should be included in a life safety plan. There are also standards that deal with detector performance, installation, calibration and maintenance, all of which are critical to effective gas detection. (See the sidebar, “Gas Detection Guidance Documents.”)
Hazardous-location standards are meant to ensure that a device can survive and perform adequately in a hazardous-classified environment. These standards vary depending on the region of the world. The IEC standards are followed as a basis by most countries, but in some cases national deviations apply.
New proposed changes to IEC standards are intended to harmonize standards worldwide for greater safety and reliability. Increased uniformity would also benefit the many global companies operating in multiple countries, which would otherwise be subject to dozens of different codes and standards.
Some standards set out the performance levels to which each life safety device should be tested. Performance testing and certification verifies that a device will operate as specified by the manufacturer under worst case standardized conditions.
Accredited third-party testing is done by experts in reliability and compliance engineering in accordance with a certification process. A number of independent organizations are accredited to issue product certifications for performance testing of gas detectors.
In addition to gas detector performance in a life safety gas system, the performance of the control architecture should be third-party certified from detection to action to validate the entire safety function relied upon. The SSC itself should also be properly rated for a hazardous classified location if intended for installation in such areas.
Choosing a Detector
There are a number of different gas detection technologies currently available. In order to choose from among them, plant personnel should consider the capabilities, advantages and disadvantages of each technology and compare these to the characteristics and requirements of the application.
It is important to recognize that toxic gas detectors are categorized by two types of equipment: Type HM (Health Monitoring) for occupational exposure equipment and Type SM (Safety Monitoring) for general gas detection equipment. For Type HM equipment, the performance requirements are focused on uncertainty of measurement of gas concentrations in the region of Occupational Exposure Limit Values (OELV). For Type SM equipment, the performance requirements are focused on alarm signaling for such purposes as safety warning and leak detection.
As for combustible gas detectors, there are two basic types of equipment: 1) performance certified equipment with focus on alarm signaling for such purposes as safety warning, and; 2) process monitoring equipment with focus on control means of a process. Only performance certified combustible gas detection equipment should be used for safety monitoring purpose.
The technologies discussed below are incorporated into what are known as fixed-detection devices, which are permanently placed in a location where gas leaks might occur. Fixed-detection devices are part of systems that protect people in a given area from harm caused by toxic and combustible gases.
Most gas detector manufacturers offer the following types of fixed-detection devices:
Point-type
Point-type gas detectors monitor a specific area or point in a facility. These detectors are used to indicate the presence of combustible or toxic gas. The gas must come into contact with the detector for sensing to occur. Point detectors require calibration for the gas type to be detected and must be regularly inspected to ensure that they are capable of performing as expected.
Point-type detectors must be strategically located for early gas detection. In critical areas, point detectors can be installed in a grid. They are mounted either high or low depending on whether the gas to be detected is lighter or heavier than air.
For detection of combustible gases, the most common choices are catalytic bead and infrared (IR) point gas detectors.
The catalytic bead gas detector is the one most frequently installed to detect combustible gas. Operation of a catalytic bead sensor is based on heat created by the catalyzed reaction between oxygen in the air and a combustible gas.
Of all available gas sensors, catalytic bead technology offers the greatest range in detection of combustible vapors. Catalytic bead sensors also offer good repeatability and accuracy, as well as fast response time and low initial cost.
IR point gas detection is based on the principle that hydrocarbon combustible gases absorb specific wavelengths of IR light. Detectors using this technology include an IR light source and a sensor to measure light intensity at IR wavelengths. If gas is present in the optical path, the IR light intensity is reduced. This change provides the data needed to calculate gas concentration.
Like catalytic bead detectors, IR detectors must be in the gas cloud for detection to occur. But unlike their catalytic bead counterparts, IR sensors can only detect hydrocarbon gases, making IR detectors not suited for settings where there is danger from hydrogen.
Nevertheless, use of IR gas detectors is growing rapidly because they compare favorably to catalytic bead detectors in other ways. For example, IR detectors are immune to contaminant poisoning, require less maintenance than catalytic sensors, and are unaffected by changes in oxygen level or high gas concentrations. And unlike catalytic sensors, some IR detectors are failsafe, meaning that the instrument checks itself and reports any internal condition preventing detection.
In addition to combustible gases, point-type gas detectors are also designed to pick up leaks of toxic gases. The detectors measure gas concentration at the point where the detector is located and give readings in ppm. Contact with the gas is required for detection to occur.
Point toxic gas detectors are placed where there is a potential for a toxic gas leak. Placement considerations include airflow in the area, as well as factors like the density and anticipated source of the toxic gas.
For toxic gases, the most common fixed-detector technologies are electrochemical (EC) cells and metal oxide semiconductor (MOS) sensors.
EC sensors consist of electrodes connected via a load resistor. The electrodes are encased in a permeable membrane that diffuses detected gas across the electrodes. Once this occurs, the assembly is submerged in an electrolyte solution.
Available in a variety of different sizes and packages, EC sensors are used to detect a wide range of toxic gases in many applications. Generally considered the main choice for toxic gas detection, these sensors offer a number of advantages, including stability, repeatability, consistency, high sensitivity and low power requirements. On the downside, use of EC sensors is restricted in very hot and very cold environments. In addition, EC sensors are generally not failsafe, so in most cases they must be routinely inspected and calibrated to ensure proper operation.
As for MOS sensors, there are many variations of this technology, which is most frequently used if the target gas is hydrogen sulfide.
MOS sensor advantages include long life, wide operating temperature range, and excellent performance in low-humidity environments.
Open path/line of sight
Open-path, or line-of-sight (LOS), gas detectors continuously monitor combustible hydrocarbon gas levels between two points. This detection technology uses a beam of light that travels between two modules. When a gas cloud passes through the beam, the gas concentration is measured. To ensure that the target gas passes through the beam, the modules must be strategically located and properly aligned. The modules themselves, however, need not be in the gas cloud for detection to occur.
Line-of-sight gas detectors continuously monitor combustible hydrocarbon gas levels between two points over long distances. This allows a large coverage area, with the result that fewer detectors may be needed. However, a limitation of this technology is that is it unable to pinpoint the location of the leak.
As with point-type detectors, it is best practice that LOS detectors are calibrated for the gas type to be detected. Typically, open-path detectors are self-monitoring and will alert users in the case of a blocked light beam or some other trouble that adversely affects their operation.
LOS detectors should be designed to withstand harsh industrial conditions, including chemical exposure and heavy vibration. Other specific product features to look for include large-area coverage, failsafe operation, infrequent calibration requirements and low maintenance.
Disadvantages of the technology can include a high initial cost and the module alignment challenges that can prevent the detectors from working properly. Ideally, the design of the chosen detector will provide the largest possible field of view, which increases the modules’ alignment tolerance, making installation faster and easier. In addition, LOS detectors do not provide a direct gas concentration measurement, measured in % lower flammable level or LFL; rather, the detector provides a gas concentration measurement integrated over the entire beam length, measured in %LFL•meter. Therefore, the detector cannot discern between a small, dense gas cloud and a large, dispersed gas cloud.
Intended to supplement rather than replace point detection systems, LOS detectors often work with point detectors to provide optimal protection of chemical facilities. In situations like this, the point detectors should be installed at or near known high-risk gas leakage points or accumulation areas to provide specific information about the level of gas present in these locations. LOS detectors should be installed at plant or process-area boundaries, where they can monitor the plant perimeter and track gas cloud movement in and out of the facility. Movement of gas clouds throughout the facility can be followed by monitoring the output signals of all the gas detectors on a workstation graphic display screen.
Acoustic
Capable of recognizing unique acoustic “fingerprints,” ultrasonic gas leak detectors sense the high-frequency sound emitted by pressurized leaking gas. In some applications, acoustic gas detection is faster than other fixed gas detection technologies because acoustic detectors do not have to wait for gas to contact them in order to “hear” a leak. Acoustic detectors are generally unaffected by rain, fog, wind or extreme temperatures, making them suitable for harsh outdoor environments.
Acoustic gas detectors are non-contact leak detectors that recognize unique sound “fingerprints.” They are ideal for locations where there is a risk of a high-pressurized gas leak.
Along with these advantages, however, come some limitations. For example, acoustic detectors cannot distinguish specific gas types. Nor can they detect toxic concentrations or the lowest gas concentration capable of producing a flash of fire in the presence of an ignition source, also known as the LFL. Therefore, acoustic detectors are best used as a complement to other gas detection methods.
When selecting an industrial acoustic gas detector, look for a high-fidelity microphone capable of continuously checking for the distinct ultrasound emitted by pressurized gas leaks across the widest spectrum of frequencies, while ignoring nuisance ultrasonic sources in the environment that could cause false alarms. The detectors should also require minimal maintenance.
Matching Detection Capabilities with Requirements
Plant owners and operators need to understand whether the area they are planning needs gas detection for risk mitigation and life safety — which, as stated earlier, requires performance certified equipment — or for process monitoring equipment to control a process. While both functions are important in a processing plant, there are significant differences between the purposes and equipment depending on the needs for gas detection.
Process monitoring detectors are integrated with a gas supply line for the sole function of continuously measuring the concentrations of gases in the supply line for process adjustments.
Life safety risk mitigation requires a uniquely qualified type of gas detector, which is used in a facility’s hazardous-area safety system. These detectors are responsible for detecting leaks of combustible and/or toxic gases for alarm signaling purposes. The gas detection equipment uses the alarm signaling for purposes such as alarm notification, releasing action, increasing ventilation, shut-down action and/or other safety functions.
Specifying and installing the right combustible and toxic gas detectors — with appropriate product approvals and performance certifications — ensures that your gas detection system will mitigate risk as intended.
Free to read
Articles are free to download. Please login to read this article or create an account.
Digital Edition
AET 28.3 September 2024
September 2024
Business News - ENVEA announces acquisition of APAQ Group - SICK and Endress+Hauser sign strategic partnership - Efforts to curb gas flaring intensify amid environmental concerns Air Monito...
View all digital editions
Events
Oct 15 2024 Galveston, TX, USA
Oct 15 2024 Kiev, Ukraine
Oct 15 2024 Poznan, Poland
Oct 15 2024 Minsk, Belarus
Oct 16 2024 Mumbai, India