Hydrogen Cooled Generator Application Note

Feb 03 2016

Application
Measurement of hydrogen purity is in a hydrogen-cooled generator during operation, start-up, and shutdown

Background
Hydrogen is used as the cooling medium in electricity generators because of its high thermal conductivity. The hydrogen absorbs heat created in the generator and dissipates that heat as the hydrogen re-circulates through a compressor and dryer system outside the generator. Hydrogen is also used in generators is due to its very low viscosity. Hydrogen reduces the amount of wind resistance and friction on the spinning generator shaft, thus increasing the generator’s efficiency.  

A reduction in hydrogen purity from 98 to 95% on a large generator can increase losses from friction and windage by up to 40%. Safety is another consideration. If air leaks into the generator, the gas can approach the upper explosive limit, possibly producing an explosion. Typically, the system is checked for leaks on a periodic basis at the generator and the tubing to and from the compressor and dryer.

Advantages
The H2scan hand held HY-ALERTA™ 500 is Hydrogen specific. The response will not be compromised by other components in the gas stream.  The portability allows checking at all locations of the generator including the bearing box, and the tubing running to and from the compressor/dryer.   With a wide range of detection, the HY-ALERTA™ 500 is used to detect leaks from 15ppm to 100%. HY-ALERTA™ 1600 is used to ensure a safe area surrounding the generator if the generator room is in a contained environment.

Additional Uses                                 
Start-up 
During start-up of a hydrogen-cooled electric generator, air in the generator is replaced with CO2. This step is taken first so hydrogen is never added to air possibly reaching the LEL. After the generator is filled with CO2 hydrogen is introduced until the generator is filled. With the hydrogen atmosphere intact, the generator can be started. 
Shut-down 
During shutdown, the hydrogen atmosphere in the generator is first displaced with CO2 and then the CO2 is displaced with Air. The Hydrogen level can be read during all phases of startup, running, and shutdown. 

Safe area monitoring in generator rooms
Hydrogen leaking into the area surrounding the hydrogen generator could make the containment room potentially explosive. HY-ALERTA™ 1600 installed in generator rooms will ensure safety operation of generators. Programmable alarms, relays and system integration are available options.

  • You can view the complete application & product benefits by clicking here

For further information or inquiries, please contact Gid Herman Tel: (661) 775-9575 ext. 606 or Russell Gruener Tel: (661) 775-9575 ext. 625.


Digital Edition

PIN 25.2 Apr/May

May 2024

Safety - Carbon monoxide toxic and flammable gas detection Analytical Instrumentation - Density: A fundamental parameter at critical stages within the petroleum sector - Advancements and...

View all digital editions

Events

IOSC 2024

May 13 2024 New Orleans, LA, USA

OGU 2024

May 14 2024 Tashkent, Uzbekistan

ISHM 2024

May 14 2024 Oklahoma City, OK, USA

REGATEC 2024

May 15 2024 Lund, Sweden

CO2 Capture, Storage & Reuse

May 15 2024 Copenhagen, Denmark

View all events